LAMTEC - Mass Flow Measurement Grid

Volume measurement of gaseous media in ducts, especially for combustion air for firing applications
With a minimum of differential pressure loss, compared to the conventional technology
Short length of inlet- and outlet-stretch for laminar flow. Long air-ducts are not required anymore
Stainless steel material
Basic temperature range up to 400 °C
Free of maintenance for use in clean air application
Rectangular and circular grid versions are available
With increased dust particles loading, flushing back can be done (option)
Connection to the Differential Pressure Transmitter by impulse piping or on customer‘s request



Technical

The grids are made by specifications of the customers. Therefore the technical data can be indicated only generally. In the case of concrete offers, and/or supplies a data sheet made particularly for the appropriate grid is provided.
 
Material: Stainless steel 1.4404
(other materials on request)
Pneumatic connection: Cutting ring connection SV12
(other types of connection on request)
Installation types: Flange connection
Welding execution
Clamping connection for „Jacobrohr“
Applicable temperature range: +5°C...+400°C
(other temperature ranges on request)
Measuring media: All not aggressive, not explosive, gaseous media with well-known density
System pressure: -0,5...+0,5 bar (negative/positive pressure)
Repetition accuracy: Generally repetition accuracy ≤ +/- 1% from measured value
Measuring accuracy: Calibrated grids on the test assembly ≤ +/- 1% from measured value
Calculated grids +/- 5% from measured value
Calibrated grids local ≤ +/- 2% from measured value