The combination-probe KS1D-HT is qualified for measuring at places or spots, which are marked by infiltrated air, as well as in multi-burner applications, for which a sole O2 measuring cannot give any statements for atmosphere or combustion process respectively a fast response is needed. It is used in applications controlling oven atmosphere at measureing gas temperatures up to 1400 °C.

It is applied to gas combustions of all types, wood- and carbon-dust combustions as well as garbage combustion plants, glow- and melting ovens and crematoriums.

Technical Data

Range of measuring O2:

0...21% O2
COe: 0...1.000 ppm COe, 0...10.000 ppm COe on request

Preciseness of measuring:

O2: +-5% of measuring value – not better than +- 0,3 Vol.%
COe: +-25% of measuring value – not better than +- 20 ppm
after prior alignment of application conditions with a CO reference measuring in a range of measuring 0...100 ppm: <= 10 ppm

Response time t60:
(60% of final value)

O2 <= 3 seconds
COe <= 9 seconds (unfiltered < 3 s)

Failure impact:

Change of temperature of measuring gas in dependency of preciseness of temperature control of ZrO2 measuring cell

Cross-sensitivity:

O2: to CO2 (15 vol. %) < 0.1 vol. % O2: to CO (874 ppm) < 0.1 vol. % O2: to CH4 (76 ppm) < 0.1 vol. % O2: to SO2 (76 ppm) < 0.1 vol. % O2: to NO (245 ppm) < 0.1 vol. % COe: to CO2 (15 vol. %) < 26 ppm COe: to O2 (1 vol. %) < 38 ppm

Allowed fuels

Residue-free, gaseous hydrocarbons, light fuel oil and brown coal / black coal

Allowed
constant exhaust gas temperature

in combination with bypass tube for flue gas temperatures up to 1200 °C (2192 °F)

Operating temperature
(KS1-D sensor)

Probe head <= 450 °C

Cable lead <= 100 °C

Connecting cable <= 100 °C