Introduction

The Team

History

Contact

 

Our Goal

Heating is colloquially considered a luxury, and more in a country like Mexico, where the heat is taken as a daily. But when it comes to specialized industrial processes or performance and production in greenhouses, heating is not a luxury, it is an absolute necessity.

And as part of an industrial process, not a question that can be left to chance, is a matter of vital importance that may mean increasing the profit margin of a company, or total loss of investment in it.

Understanding this fundamental need, in Van Triest Engineering Group works to give the customer not only products of the best brands with proven quality, but also the necessary technical support for users who decide not see your confidence in your investment risk.

The mission of Van Triest Engineering is to provide the best product, best support and better care.

 

 

Combined O2 and CO/H2 measuring

Measuring directly inside flue-gas

Applicable up to 1200 °C

Independent of infiltrated aire (COe)

Ex design

 

 

 

The Lambda transmitter LT3 in connection with the combination probe KS1D is developed for simultaneous measurement of O2 concentration and oxidizing gas elements (CO/H2), displayed as COequivalent (basically in exhaust gases of combustion plants within hyperstoichiometric ranges (λ > 1).

The display and handling of the LT3 is managed via user interface inside the front door (belongs to standard delivery), with the following functions:

Display of O2 and CO measurement values

Password entry

Informationen about probe and fuel, for warnings and failures, for software versions, CRC and serial number

Calibration of measurement

Setup (maintenance, filter time, analogue output, probe exchange, display)

Technical Data

Housing:

Sheet steel

Protection type following  DIN 40050

IP66, without display
IP54, with embedded start-up assistant inside front door

Dimensions (HxBxT) mm

300 x 300 x 120

Color

Grey, RAL 7035

Weight

appr. 6kg

Ambient temperature
operation:

-5 °C ... + 60 °C

Ambient temperature
transport and storage:

-20 °C ... + 70 °C

Power supply:

120 VAC / -30%...230 VAC / +10%, 50...60Hz

Power consumption:

30W (normal operation)
69W (heating)

Resolution O2:

0,1 Vol. % O2  in the range of 0...18 Vol. % O2
1 Vol. % O2  in the range of 18...25 Vol. % O2

Resolution COe:

1ppm in CO-range of 0…1000ppm

Preciseness of measuring:
(with combination probe KS1D)

O2:   ±5% of measurement value 
(max ± 0,3 Vol. % O2)

COe:  ±25% of measurement value
(not better than +/- 20 ppm after prior calibration for application conditions with a CO-reference measuring)

Setting time (60 % time):

O2:   T 60 < 10 s
COe: T 60 < 2 s

Time for readiness
with KS1D (cold start-up)

appr. 10min after „POWER ON“
(Initial start-up appr. 60min)

Analogue output, via analogue output module:

Analogue output  1 (O2 measurement value)
- Range of setting:   0…25 % O2
- Factory setting 0…10 Vol.% O2 -> 4…20 mA

Analogue output 2 (CO-measurement value)
-  Range of setting: 0…1000 ppm
- Factory setting 0…1000 ppm -> 4…20 mA

Digital outputs
via digital output module:

optional

Control element:

Integrated LT3 User Interface with LCD-graphic display 45x27 mm (BxH)

External start-up assistant with LCD-graphic display 60x32 mm (BxH) (Option)

Interface:

LAMTEC System Bus (LSB)