FMS

Combustion Management System

FMS - Combustion Management System

Burner control

Electronical compound, up to 5 channels

Universal field bus to interface process control

PC/Modem interface

Integrated load controller

Integrated leakage test

Integrated CO/O2 controller

Sliding controlled fuel changed

Simultaneous combustion of 2 fuels with a variable mixture ratio

Blow out of the burner lance

Purpose:
This is the complete burner controller that meets all requirements; type-examination tested. By using a different relay unit and a software module, the VMS compound management system becomes the FMS combustion management system. Thus, the electronic compound regulator comes with a burner controller. This integration saves a great deal in terms of wiring overheads and reduces the number of error sources. Commissioning the system becomes simpler.

The FMS contains all VMS functions. However it also contains the combustion controller, and if necessary, a leakage monitor too. Together, all these functions reduce the required number of external instruments to a minimum, thus creating a price/performance ratio without peers. When using the FMS with integral Leakage monitor, Output regulator, and possibly RPM speed feedback, everything needed for combustion control is integrated into one unit. Safety chains, Sensors, and monitors are linked directly to the FMS. Additional external regulators or monitoring devices are hardly needed anymore.

Visual data and operation are the same as in the VMS. Control of the magnetic valves, the ignition transformers, the ventilators, etc takes place via a special relay module. This allows valves up to 2 A to be switched directly. The FMS has 16 digital inputs, of which 3 are inputs for separate safety chains. Thus, external error sources can be differentiated, identified and displayed.

The controller can be adapted to the widest range of different tasks through simple parameter settings. Many of these can be adjusted on site. Each permitted flame monitor can be addressed via a floating-potential contact.

Technical Data:

Voltage supply:

230 VAC +10 % -15 % 50/60 Hz
115 VAC +10 % -15 % 50/60 Hz (option)

Ambient temperature
Operation:

+0 °C … +60 °C

Ambient temperature
Transport and storage:

-25 °C … +60 °C

Resolution per analog input:

999 digit, 10 bits

Three-point-step:

Via external relay modules
type 660R0013 up to 50 mA (40 Nm)
type 660R0131 more than 30 Nm
up to 3,1 A

Recommended run-time of the servomotor:

30 s … 60 s

Constant outputs

0 … 10 V > 5 kΩ

Load:

0/4 … 20 mA < 600 Ω

Digital signal inputs:

16 via floating contact
24 VDC

Number of curve-sets:

2 per channel (e.g. for oil/gas dual-fuel burner) optional 4 or 8

BUS connection:

Via 25-pole sub-D socket, communication processor optional for the systems:

  • Interbus-S (Phoenix)
  • PROFIBUS
  • Modbus
  • CANopen

Download: